High Voltage Switchgear

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers 3 deliver within days

  • seat:

    Zhejiang

  • Validity to:

    Long-term effective

  • Last update:

    2022-01-17 17:18

  • Browse the number:

    4

Send an inquiries

Company Profile

NINGBO TIAN AN JINGHUA POWER TECHNOLOGY CO., LTD.

By certification [File Integrity]

Contact:Tony ma(Mr.)  

Telephone:

Area:Zhejiang

Website:http://www.voltageswitchgear.com/ http://voltageswitchgear.lanniao-cn.com/

Product details


600~2000A KYN61-40.5 Power Distribution Switchgear / metal clad switchgear



 



Construction of 600~2000A KYN61-40.5 Power Distribution Switchgear / metal clad switchgear:



The design of KYN61 switchgear conforms to regulations for metal clad drawable switchgear in GB3906. It is mainly composed of two part, the cubicle body and the handcart. The cubicle divided into four sole compartment, the circuit compartment, bus bar compartment, cable compartment and gauge compartment. The degree of protection for the cubicle is IP4X, and IP2X for the compartments. The handcart includes the main switch (or other functional components) and support part.



 



Installation of 600~2000A KYN61-40.5 Power Distribution Switchgear / metal clad switchgear



To ensure the installation quality of the basic components, the frame levelness should be 1mm/1m.



For the switchgears in single line, the recommended width of aisle before the line is 2.5m, for the double lines of switchgear, the recommended width of aisle between the lines is 3m.



According to the requirements of the project and drawings, put the switchgear to the predetermined location, and arrange the rank from middle position.



The transportation should be carried out by using of specific equipments, such as crane or truck, but the using of rollers or levers is seriously forbidden, and the transportation of the enclosure with the handcart mounted in is seriously forbidden, the handcart should be put in until the accomplish of the installation of enclosure.



Take away the cable seal boards.



Following up the above steps, to install the switchgears one by one, the unevenness should no more than 2mm.



The switchgears can be coupled with or welded together firmly with the earth basic components.



 



Main technical specification of 600~2000A KYN61-40.5 Power Distribution Switchgear / metal clad switchgear














































Parameters

Unit

Specification

Rated Voltage

KV

40.5

Lighting impact withstand voltage

KV

185

Rated Current

A

630,1250,1600,2000

Rated short circuit current

KA

25,31.5,40

Rated Short Circuit Closing Current

KA

63,80

Rated Dynamic Stable Current

KA

63,80

Protection Grade

 